| Controller
Symptom |
Possible
Cause (s) |
Corrective
Action |
|
Control will not turn pump (or pool valve) on or off
in automatic mode but turns on in manual mode. |
1. Defective temperature
sensor
2. Defective control
3. Open/short in sensor wiring
4. Sensor(s) not properly located |
1. Replace defective sensor
(s)
2. Replace control
3. Repair / replace wires
4. Relocate sensors |
|
Shuts off at the wrong high limit or will not shut
off at all. |
1. Defective sensor
2. Sensor poorly located
3. Defective control |
1. Replace sensor
2. Relocate sensor
3. Replace control |
|
Pump runs after dark but eventually shuts off. |
1. Defective sensor (s)
2. Sensor poorly located/insulated |
1. Replace sensor
2. Relocate sensor/insulate |
|
Pump cycles on and off briefly after dark |
1. Thermosyphoning |
1. Replace / install check
valve in feed and return lines. |
|
3-Way pool valve turns continuously (pool or spa) |
1. Bad micro switch or micro
switch out of alignment. |
1. Replace or adjust micro
switch |
|
3-Way valve wont turn even in manual mode (pool or
spa) |
1. Bad micro switch
2. Valve jammed with debris
3. Defective motor |
1. Replace bad micro switch
2. Clear obstruction
3. Replace valve |
|
Short cycles at high limit (spa) |
1. High limit sensor is too
far from the spa |
1. Locate high limit sensor
closer to the spa |